Product Name: HCS6300 Transformer Loss Capacity Tester
Category: Transformer Comprehensive Test Series
Detailed Introduction
Product Introduction
HCS6300 Transformer Loss Capacity Tester is an instrument specially used for measuring the capacity of distribution power transformers, transformer no-load and short-circuit loss.
Functional features
※ Capacity measurement: The instrument has a built-in rechargeable battery. The instrument itself can output a three-phase sine wave inverter power supply. It can measure the capacity of the distribution transformer and determine the model without any external power supply. At the same time, it displays the transformer impedance voltage and the load loss converted to the rated temperature and rated current;
※ No-load loss measurement: The instrument displays three-phase voltage, three-phase current, and three-phase power. The instrument displays the distortion rate of the applied power waveform, automatically calculates the no-load loss of the transformer converted to the rated voltage and corrected for waveform distortion, and displays the model of the distribution transformer core;
※ Load loss measurement: Displays three-phase voltage, three-phase current, and three-phase power, automatically calculates the transformer impedance voltage percentage, converts to the load loss at the rated temperature and rated current, and automatically determines the coil model of the distribution transformer;
※ Single-phase measurement: It can be used to check the defects of the single-phase transformer or when there is no three-phase electricity on site. The instrument can record the data of three single-phase measurements, and can calculate the no-load current, no-load loss, impedance voltage and load loss of the transformer according to the different connections of the transformer;
※ It can be measured directly within the measurement range allowed by the instrument. If it exceeds the measurement range, it can be connected to an external voltage and current transformer. The instrument can set the transformation ratio of the external voltage and current transformer and directly display the applied voltage and current values;
※ The instrument has a large-screen LCD display, which can display three-phase voltage, three-phase current, three-phase power, three-phase average voltage, average current, three-phase total power and related data on the same screen. The instrument has Chinese menus and Chinese prompts, and the operation is simple;
※ The instrument is equipped with an RS232 interface, which can communicate with the computer through a data cable;
※ The instrument has a built-in printer, which can print and display data, and has a built-in memory, which will not be lost when the power is off. The instrument can store 20 sets of data;
※ Permanent calendar and clock functions can be used for time calibration.
| Technical Parameters | |
| Measuring range | Voltage: 0~500V |
| Current: 0~50A | |
| Capacity: 30kVA~65000kVA | |
| Accuracy | Voltage, current: 0.2 level |
| capacity | ±10% |
| power | 0.5 level (cosφ>0.1), 1.0 level (0.02<cosφ≤0.1) |
| Overall dimensions | 360mm×320mm×235mm |
| Instrument weight | 10kg |
| Conditions of Use | |
| Ambient temperature | -10℃~50℃ |
| Ambient humidity | ≤85%RH |
| Working power supply | AC220V±10% |
| Power supply frequency | 50±1Hz |