Product name: HCYZ-XA transformer on-load switch AC/DC parameter test device
Category: Transformer comprehensive test series
Detailed introduction
Product introduction
HCYZ-XA contains two methods to measure and diagnose the characteristics of large and medium-sized transformer on-load tap changers, the first is the DC method, and the second is the AC method.
Functional features
※ Can compare the synchronization of AC and DC measurements during the on-load switch switching process;
※ Possess AC and DC comprehensive measurement capabilities. In one instrument, various DC and AC parameters of on-load tap changers can be measured, such as switch selection, whether there are breakpoints during the switching process, AC/DC transition waveforms, transition time, transition resistance, three-phase synchronization, etc.
※ The software has data functions and comprehensive measurement result analysis. Users can use the back-end software and various function buttons to analyze the resistance value of each point and each segment in the waveform, the time of each segment, and the three-phase synchronization, etc. Through analysis, the changes in various parameters of the three-phase switch at each moment during the switching process can be understood, and the waveforms can also be printed, stored, and historical waveforms can be checked for analysis and comparison;
※ The software is highly intelligent, which is convenient for fast on-site parameter input and more convenient testing;
※ With an expert analysis system, it automatically diagnoses the status of the on-load tap changer;
※ 6 independent and completely isolated 16-bit high-precision high-speed synchronous measurement channels;
※ The software and hardware anti-interference technology is used to ensure the stability and accuracy of the measurement.
| Technical Parameters | |
| Internal output AC inverter source | |
| Power supply frequency | Adjustable frequency point (40Hz-60Hz range) |
| Output voltage | Three-phase 800V (effective value, varies with load) |
| Output capacity | Rated 1000VA, maximum instantaneous output 1500VA (lasting 200ms, overload protection does not work) |
| Voltage waveform distortion rate | <2% |
| Voltage phase angle | 120°, phase angle difference is not more than 120°±1° |
| Internal output DC constant current power supply | |
| Opening voltage | 24V |
| electric current | 1A, 0.5A optional |
| Resistance test range | 0.5-40Ω; |
| Test precision | ±(2% reading + 2 words) |
| Time test range | 1-240ms |
| Test precision | ±(2% reading + 2 words) |
| Sensor accuracy | |
| Voltage and current sensor precision | 0.2级 |
| Sensor response speed | ≤15μs |
| Voltage range0V-800V (effective value) | |
| Current range | 0mA-100mA (effective value), 0A-5A (effective value); |