Product name: HCR1000 transformer winding deformation tester
Category: Transformer comprehensive test series
Detailed introduction
Product Introduction
HCR1000 Transformer Winding Deformation Tester (Frequency Response Method) is used to test power transformers with voltage levels of 6kV and above and other transformers for special purposes. Power transformers are inevitably subject to various fault short-circuit current shocks or physical impacts during operation or transportation. Under the strong electric force generated by the short-circuit current, the transformer winding may lose stability, resulting in permanent deformation such as local distortion, bulging or displacement, which will seriously affect the safe operation of the transformer.
Functional characteristics
The test can be carried out without covering or disassembling the transformer;
The currently popular sweep frequency method is used for measurement;
This instrument can measure transformers above 6kV;
The split structure is adopted, and the test host and the main control computer are connected by USB, which is plug-and-play;
The on-site wiring is simple and easy to use;
The measurement dynamic range is wide: -100dB~20dB;
The analysis software is powerful, and the software and hardware indicators meet the national standard DL/T911-2004.
技术参数
◆ The signal output is a standard sine wave, with a maximum amplitude of ±10V and an output impedance of 50Ω;
◆ Quantization accuracy of the acquisition channel: 12 bits;
◆ Maximum static error of the acquisition channel: 0.5%;
◆ Maximum storage capacity per channel: 64K samples;
◆ Maximum sampling rate per channel: 20Msps;
◆ Input impedance of the acquisition channel: 1MΩ;
◆ Sweep frequency measurement range: 1k-2000kHz;
◆ Sweep mode: Linear or logarithmic distribution sweep frequency measurement method;
◆ Sweep frequency accuracy: The frequency accuracy of the sine signal output by the signal source is not greater than 0.01%.