Product name: HC8022 SF6 gas leakage online monitoring system
Category: Substation intelligent online monitoring system

Detailed introduction

HC8022 SF6 gas leakage online monitoring system is mainly used in 35kV SF6 switch room and 500kV, 220kV, 110kV GIS room in substation, and real-time monitoring of SF6 gas leakage and oxygen content in the air in the SF6 combined electrical equipment room environment.

This system can monitor up to 64 monitoring points in the environment, and can also use multiple main control units for networking control, and communicate with the power station automation system. Effective monitoring of indoor SF6 concentration and O2 concentration improves the safety of unmanned substation operation, especially the personal safety of daily patrol and maintenance personnel is reliably guaranteed.

The system is divided into three modules: (1) gas sampling module, which is mainly used to complete the gas sampling function at each measuring point; (2) gas analysis module, which is mainly used to complete SF6 quantitative analysis, O2 quantitative analysis, temperature and humidity measurement functions; (3) host and auxiliary function module, which is mainly used to complete the coordination of various modules, display, alarm, fan start and other functions.

 

Technical Parameters
1. Gas sampling module Functions and parameters
Built-in 5μ pore filter, can effectively filter air impurities
Detection point 12 channels + 1 channel zero point calibration, can be expanded to 32 channels
Sample gas flow rate 3L/min gas pipeline can be several hundred meters long
Sampling pipeline PVC pipe with outer diameter Φ6 and inner diameter Φ4 can quickly replace the gas in the pipeline;
Sampling method Long life electromagnetic pump, low noise
Working power supply AC185v~250v, anti-wave and lightning protection function
size 340mm×420mm×100mm
2. Gas analysis module Functions and parameters:
Automatically strengthen the tracking of suspicious measurement points to effectively prevent false alarms
SF6 detection range 0~1500ppm, accuracy not less than 50ppm, resolution: 1ppm
O₂ detection range 0~25.0% Error: <0.5% Resolution: 0.1%
Temperature display range -20~+99℃
Humidity display range 0~99%RH
Working power supply AC185v~250v, anti-wave and lightning protection function
Support on-site display Large screen Chinese display
size 290mm×380mm×135mm
3. Technical indicators
Support RTU remote fan start function
Support infrared human body detection, automatically start the fan or voice prompt
SF6 concentration detection range 0~1500ppm
SF6 gas detection range ±5% setting value
Oxygen concentration detection range 0~25%
Oxygen measurement accuracy Less than 0.5% (0.4%, O₂ at 21%)
Hypoxia alarm threshold 18.0% (adjustable)
Temperature display range -20~99℃
Humidity display range 0~99%RH
Detection point Standard configuration 12 points (expandable to 32 points)
Data logging function Automatic recording of alarm events, massive storage, automatic update
Alarm output Relay open contact output, can be connected to RTU, and supports RS485 alarm output

We look forward to serving you

Contact us today and let us start fundamentally transforming your business.