Product Name: HC8021GIS Partial Discharge Online Monitoring System
Category: Intelligent Online Monitoring System for Substations
Detailed Introduction
Product Introduction
HC8021GIS Partial Discharge Online Monitoring System is a new generation of high-performance digital partial discharge online monitoring device that uses sensor technology, signal processors, computers and other technical means and algorithms. It can operate for a long time and monitor the partial discharge of GIS in real time during operation. It can timely warn of abnormal insulation status and discharge faults of GIS, provide necessary guidance data for the normal operation of GIS, and improve the reliability, safety and effectiveness of GIS operation.
Functional Features
※ Strong anti-interference ability and accurate monitoring data;
※ Several monitoring devices in the station can operate independently, and the data are recorded separately;
※ Provide multiple alarm methods: mobile phone SMS alarm, sound and light alarm, etc.;
※ Realize remote data transmission through fieldbus, telephone network or Internet network, and conduct high voltage
※ Remote online monitoring and operation analysis of electrical equipment;
※ The background management software has powerful partial discharge trend analysis function.
| Technical Parameters | |
| Measurement channels | 2ch |
| Sensitivity | 1 channel 100pC (electrical signal) |
| 2 channels 10pC (electrical signal) | |
| Measuring range | 100pC~80000pC (electrical signal) |
| Maximum error | 25% (electrical signal) |
| Monitoring frequency band | 1 channel :10kHz~5MHz |
| 2 channel :40kHz (High Pass Filter) | |
| 300kHz (Low-pass filter) | |
| Wideband Current Transformer | Installation location: External, shell grounded |
| Fixing method: open card installation | |
| Signal transmission medium: 50 ohm coaxial cable | |
| Bandwidth: 10kHz~5 MHz | |
| GIS online monitoring ultrasonic sensor | Installation location: External, on the outer wall of the housing or the connecting flange |
| Fixing method: special fixing belt (the sensor has its own magnetic adsorption) | |
| Signal transmission medium: 50 ohm coaxial cable or optical fiber | |
| Frequency response bandwidth: 2 kHz ~ 80 kHz | |
| UHF Sensor | Installation location: external, at the connecting flange |
| Fixing method: special fixing belt | |
| Signal transmission medium: 50 ohm coaxial cable | |
| Bandwidth: 300MHz~1.5GHz (can be selected according to site conditions) | |
| Ambient temperature | -20~50℃ |
| Working power supply | Single phase, AC220V±10% |
| Power supply frequency | 50±0.5Hz |