Product name: HCKD-II Vacuum Tester
Category: High Voltage Equipment Comprehensive Test Series

Detailed introduction

The common method to judge whether the vacuum degree of vacuum tube is deteriorated is the power frequency withstand voltage method. This method can only judge the arc extinguishing chamber with serious vacuum deterioration. When the vacuum degree deteriorates to 10-2~10-1Pa, although the breakdown voltage has not decreased, the arc extinguishing chamber is unqualified. The HCKD-Ⅱ vacuum tester adopts a new excitation coil and uses the magnetron discharge method to test the vacuum degree of the arc extinguishing chamber without disassembling the arc extinguishing chamber. At the same time, a microcomputer is used for synchronous control and data acquisition processing, so that the on-site test sensitivity of the vacuum degree of the arc extinguishing chamber reaches 10-5Pa. It is widely used in departments using vacuum switches such as electricity, steel, petrochemicals, textiles, coal, and railways.

Functional features

The instrument adopts a new excitation coil and data processing method to achieve non-disassembly measurement of vacuum degree;

Easy to use, simple to operate, and high test accuracy;

It has a complete protection circuit and strong anti-interference ability;

This instrument is a multi-purpose machine that can measure vacuum demagnetization of various models.

Technical Parameters
Detection range 10-5~10-1 Pa
Measurement accuracy 10-5~10-4 Pa 15%
10-4~10-3 Pa 15%
10-3~10-2 Pa 10%
10-2~10-1 Pa 10%
Magnetic field voltage 1700V
Pulsed electric field high voltage 30kV
Sampler Magnetron Coil
Switch tube opening distance when testing vacuum Normal use distance
Dimensions 420mm×320mm×280mm
Conditions of Use
Ambient temperature -20℃~40℃
Ambient humidity ≤90%RH
Working power supply AC220V±10%
Power frequency 50±1Hz